| Plan Review Notes For Permit 02011590 |
| Permit Number |
02011590 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-28 00:00:00 | DENIED | | | REFERENCE: FLA. BLD. CODE - 2001 - POOLS | | | | | | 1) 424.2.6.2 EQUIPMENT LIST WITH MFG. | | | CUT SHEETS. | | | 2) 424.2.6.4 MORE MFG. INFO REQUIRED, | | | GIVE MFG RECOMMENDATIONS PLUS LISTING | | | AGENCY APPROVAL. | | | 3) 424.2.6.6.2 SHOW ANSI/ASME A112.19.8M | | | SUCTION FITTINGS COVERS INFO FOR ACCEPT- | | | ANCE. | | | 4) 424.2.6.6.3 VENT NOT SHOWN FOR SPA | | | MAIN DRAIN OR VACUUM LINE. ARE #'S 1 OR | | | 2 BEING USED? PLEASE PROVIDE DETAILS. | | | 5) 424.6.6.5 6" TO 12" BELOW MIN WATER L | | | LEVEL. SHOW DETAILS OR STATE ON PLANS. | | | 6) 424.2.14.2 WATER RETENTION, NOT ABLE | | | TO RETAIN WATER IN HEATER WITH ONLY ONE | | | VALVE LOCATED WHERE SHOWN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|