Plan Review Notes
Plan Review Notes For Permit 02011587
Permit Number 02011587
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-02-06 00:00:001) PLEASE PROVIDE THIS OFFICE A WRITTEN
 PLAN ON HOW THE BUILDING WILL BE
 DEMOLISHED. SINCE THE BUILDING CONTAINS
 A LARGE AMOUNT OF COMBUSTIBLE MATERIAL
 THE FIRE SPRINKLER SYSTEM IS TO REMAIN
 ACTIVE UNTIL SUCH TIME AS THE
 COMBUSTIBLE MATERIAL IS REMOVED FROM THE
 BUILDING.
 2) THE FIRE SPRINKLER SYSTEM IS NOT TO
 BE DEMOLISHED UNTIL APPROVAL IS GRANTED
 BY THE CITY FIRE MARSHAL AND THE
 DIRECTOR OF CONSTRUCTION SERVICES.
 3) ADEQUATE MEANS OF EGRESS ARE TO BE
 PROVIDED DURING DEMOLITION ACTIVITIES.
 4) DEMOLITION ACTIVITIES ARE TO BE
 CONDUCTED IN ACCORDANCE WITH NFPA 241,
 THE STANDARD FOR SAFEGUARDING,
 CONSTRUCTION, ALTERATION AND DEMOLITION
 OPERATIONS, 1996 EDITION.
 5) NO HOT WORK IS TO PERFORMED IN THE
 BUILDING UNTIL APPROVED BY THE FIRE
 PREVENTION BUREAU IN ACCORDANCE WITH
 NFPA 51 B, THE STANDARD FOR FIRE
 PREVENTION DURING CUTTING, WELDING AND
 OTHER HOT WORK, 1999 EDITION.
 6) PORTABLE FIRE EXTINGUISHERS ARE TO
 REMAIN ON SITE DURING DEMOLITION
 ACTIVITIES.
 7) NO FIRE HYDRANTS ARE TO BE OBSTRUCTED
 BY DEMOLITION MATERIAL OR EQUIPMENT.
 8) NO FUEL TANKS ARE TO BE PLACED ON
 THE SITE WITHOUT APPROVAL OF THE
 FIRE PREVENTION BUREAU.
 9) NO FLAMMABLE LIQUIDS OR GASES ARE
 TO BE STORED WITHIN THE BUILDING
 DURING DEMOLITION ACTIVITIES.
 10) NO SMOKING SIGNS ARE TO BE PLACED
 WITHIN THE BUILDING DURING DEMOLITION
 ACTIVITIES.
 11) COMBUSTIBLE WASTE AND TRASH. THESE
 MATERIALS ARE NOT ALLOWED TO ACCUMULATE
 WITHIN OR OUTSIDE THE BUILDING.
 12) ADEQUATE FIRE WATCH AND SECURITY
 PROTECTION ARE TO BE PROVIDED FOR THE
 SITE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910