| Plan Review Notes For Permit 02011505 |
| Permit Number |
02011505 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-30 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW CIRCUIT #`S AND | | | WHERE THEY COME FROM. TWO BAYS CANNOT | | | COME FROM ONE SIDE ONLY? PLEASE CLARIFY | | | PANEL(S) LOCATIONS. | | | | | | 2)NOTE: PLEASE NOTE THAT PER FS/FAC. | | | PLANS THAT ARE COPIES OF SIGNED AND | | | SEALED DOCUMENTS CAN NOT BE SUBMITTED. | | | PLEASE ONLY USE THAT SECTION OF DRAWING | | | /HAVE PLANS DONE BY THE ARCH OF RECORD | | | OR DRAW PLAN SEPARATE. | | | FS481.221 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|