2002-02-25 00:00:00************BUILDING PROVISO************
  
 SBC 104.2.2
  
 1. DRAWINGS S1: CLARIFY 6 #7'S @ FC/6.
 DRAWING A/S2 REFERENCES FC/5 VERTICAL
 BARS AS 5 #7'S.
  
 2. GENERAL NOTES STATE SOIL PRESSURE AS
 2000 PSI.SHOULD BE 2500 PSI.NEED
 SOIL REPORT STATING CORRECT PRESSURE.
  
 THE ABOVE PROVISOS HAVE BEEN NOTED ON
 SEVERAL PREVIOUSLY REVIEWED MODEL 401
 PLANS.ARCHITECT MUST CORRECT THE
 DRAWINGS AND RESUBMIT THE CORRECT
 DRAWINGS TO THE BUILDING DEPT.
  
  