Plan Review Notes
Plan Review Notes For Permit 02011428
Permit Number 02011428
Review Stop P
Sequence Number 2
Notes
Date Text
2002-03-06 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) WATER HEATERS LOCATED IN CEILING OR
 ON A SHELF SHALL HAVE A PERMINATE SHIPS
 LADDER INSTALLED. SEC 501.7
  
 2) HEATER PANS SHALL HAVE A 1" PAN DRAIN
 MINIMUM. SPC SEC 507.8.2
  
 3) SERVICE PLATFORM REQUIRED FOR HEATER
 IN CEILING. MIMIMUM 30"X30"REQUIRED
 AT SERVICE SIDE OF HEATER. SMC-97 SEC
 304.4.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377