| Plan Review Notes For Permit 02011428 |
| Permit Number |
02011428 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-13 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 63-89. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS AS PER 1997 | | | SMC 406.1 & NFPA 90A 4-4.4.3. | | | | | | 3.CONDENSATE DRAIN IS NOT ADDRESSED | | | ON PLAN.PLEASE INDICATE LINE SIZE, | | | MATERIAL AND TERMINATION ON PLAN. | | | SHALL COMPLY WITH COUNTYWIDE AMMEND- | | | MENTS 1994 SPC 804.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|