| Plan Review Notes For Permit 02011428 |
| Permit Number |
02011428 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-06 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE CLARIFY SHOW WINDOW | | | OUTLETS PER 210-62. /220-12A | | | | | | 2)NOTE: PLEASE NOTE MISSING LOAD | | | CALCULATIONS PER 220-3,220-10,220-11, | | | 220-13 AND THEN CONTINUOUS LOADS AT 125% | | | | | | | | | 3)NOTE: PLEASE SHOW TRACK LIGHTING LOAD | | | CALCUALTIONS PER 220-12B | | | | | | 4)NOTE: PLEASE CLARIFY IF SERVICE IS | | | NEW OR EXISITNG? PLEASE NOTE THAT NOTE | | | ON RIGHT HAND CORNER OF RISER DIAGRAM | | | SAYS "EXISTING" SERVICE? PLEASE CLARIFY. | | | | | | 5)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN | | | DISCONNECT AND PANEL. 250-122 | | | | | | 6)NOTE: PLEASE CLARIFY 320' SHOWN FROM | | | METER TO PANEL FOR VOLTAGE DROP. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|