| Plan Review Notes For Permit 02011419 |
| Permit Number |
02011419 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-07 00:00:00 | ************* PROVISO/REVISION ******** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CIRCUITS | | | NEED TO BE SHOWN ON PLANS AND NEED TO | | | CORRELATE WITH PANEL SCHEDULE. | | | | | | 2)NOTE: PLANS NEED TO CLARFIY LOAD | | | FOR WASHER/DRYER. PLANS SHOW COMBO UNIT | | | AND PANEL SHOWS DRYER ONLY? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE FINAL. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|