| Plan Review Notes For Permit 02011349 |
| Permit Number |
02011349 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-14 00:00:00 | *******************DENIED*************** | | | | | | PLANS RVIEWED UNDER THE 1997 STANDARD | | | MECHANICAL & BUILDING CODE. | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 3.PLEASE INDICATE THE THE FIRE | | | RESISTANCE RATING OF THE MECHANICAL | | | ROOM. | | | | | | 4.IDENTIFY LOCATION OF ALL FIRE | | | DAMPERS ON PLAN AS PER 1997 SMC | | | 610.6. | | | | | | NO COMBUSTIBLES ABOVE THE CEILING IN THE | | | RETURN AIR PLENUM. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|