| Notes |
| Date |
Text |
| 2002-01-29 00:00:00 | 1) DOOR 100 TO COMPLY WITH THE FLORIDA | | | FIRE PREVENTION CODE, NFPA 101, THE | | | LIFE SAFETY CODE, 2000 EDITION, SECTION | | | 7.2.1.9. | | | 2) PLEASE INDICATE INTERIOR FLOOR FINISH | | | IN CORRIDORS AND EXITS. | | | 3) PLEASE INDICATE LOCATIONS OF PORTABLE | | | FIRE EXTINGUISHERS. | | | 4) NO FIRE SPRINKLER DRAWINGS PROVIDED. | | | 5) ADDITIONAL EXIT SIGNS REQUIRED TO | | | DIRECT PERSONS TO THE REAR EXITS. | | | 6) NEW CANVAS CANOPY TO BE FIRE | | | RETARDANT. | | | 7) PLEASE INDICATE LOCATIONS OF PORTABLE | | | FIRE EXTINGUISHERS. | | | 8) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM REMODEL. | | | 9) BUILDING ADDRESS REQUIRED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|