| Plan Review Notes For Permit 02011286 |
| Permit Number |
02011286 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-04-24 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) REFERENCE CODE FOR PLUMBING IS STAND- | | | ARD PLUMBING CODE 1994, NOT S.F.B.C AS | | | INDICATED. | | | 2) SHT A-1 FROM PREVIOUS REVIEW, FLOOR | | | DRAIN NOT VENTED PROPERLY IN WOMENS REST | | | ROOM ON THE SANITARY RISER DIAGRAM. | | | PLEASE CORRECT AND RESUBMIT. | | | 3) SHT A-2 FROM PREVIOUS REVIEW, DRINK- | | | ING FOUNTAIN, NO REFERENCE TO HI - LOW | | | TRAJECTORY IN FACBC-97 SEC 4.1.3(10). | | | PLEASE SUBMIT DETAIL FOR COMPLIANCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|