| 2002-02-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 02011286 |
| | 4925 N MILITARY TRL |
| | CONT: TRANSEASTERN PROP |
| | TEL: NOT LISTED |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | |
| | 1)- SBC 104.2.2 ADDITIONAL INFORMATION |
| | REQUIRED, THE PLANS DO NOT INDICATE |
| | UNDER WHAT CODE CRITERIA THEY ARE DESIGN |
| | ED TO? |
| | 2)- THE DESIGN CRITERIA, PARAMETERS & |
| | ASSUMPTIONS, MEAN ROOF HEIGTH, BASIC |
| | WIND VELOCITY PRESSURE, ROOF DEAD LOADS |
| | MINIMUM SOIL BEARING AND IF ARCH. REVIEW |
| | ED FOR SHEAR WALLS. |
| | 3)- MISSING SOILS REPORT. |
| | 4)- SHEET A-2 DOORS 1 & 1-A INDICATE |
| | (W)6'-0"X(H)8'-0", THE PRODUCT APPROVAL |
| | REPORT IS APPROVED UP TO (H)7'-0". |
| | 5)-DOOR 1-A PRODUCT REPORT IS NOT APPROV |
| | ED FOR SIDE LITE INSTALATION. |
| | 6)- SHEET A-4 THE GABLE END DETAIL INDI- |
| | CATES A DETAIL 8/D-1? MISSING. |
| | 7)- WIND PRESSURES TO BE SHOWN ON ELEVAT |
| | IONS FOR DOORS / WINDOWS (EXTERIOR). |
| | 8)- SHEET A-4 FRONT FRENCH DOORS, SHOULD |
| | THERE BE A L-1 BETWEEN THE TRANSOM & |
| | DOOR. |
| | 9)- A-5 KITCHEN: PUBLIC & COMMON USE |
| | KITCHENS MUST BE USABLE AND MEET THE |
| | REQUIREMENTS IN THE GUIDELINE FOR KITCH- |
| | ENS IN ANSI 4.32 COULD BE FOLLOWED. |
| | FL .ACC. REACH RANGES 4.2.6. |
| | 10)- FAIR HOUSING AS WELL AS FL ACC CODE |
| | AT LEAST ONE ACCESSIBLE ROUTE SHALL CON- |
| | NECT ACCESSIBLE BUILDINGS, FACILITIES, |
| | ELEMENTS AND OTHER SPACES THAT ARE ON |
| | THE SAME SITE. FL ACC 4.3.2(2). |
| | THE FRONT AND REAR ELEVATIONS INDICATE |
| | CHANGE OF GRADE GREATER THAN 1/2". |
| | THERE APPEARS TO HAVE A SIDEWALK THAT |
| | CONNECTS THE VOLLEYBALL COURT, ALSO THE |
| | POOL DECK BUT NOT THE TOT LOT. |
| | 11) COUNTY IMPACT FEESARE TO BE PAID |
| | BEFORE ISSUANCE OF PERMIT. |
| | 12) RADON FEES ALSO DUE BEFORE ISSUANCE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |