| Plan Review Notes For Permit 02011267 |
| Permit Number |
02011267 |
|
| Review Stop |
FS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-22 00:00:00 | A) RED LINE ON PLAN INDICATES THAT A | | | PORTION OF THE UNDERGROUND FIRE LINE | | | WILL BE LOCATED UNDER THE BUILDING. THIS | | | IS NOT ALLOWED BY CODE AND WILL NOT | | | BE PERMITTED TO BE DONE IN THIS MANNER. | | | PLEASE ENSURE THAT THE FIRE LINE IS | | | NOT LOCATED UNDER THE BUILDING. | | | B) BACKFLOW DEVICE REQUIRED TO HAVE | | | TAMPER SWITCHES, LOCKS AND CHAINS. | | | C) SPARE SPRINKLER HEAD BOX AND WRENCH | | | REQUIRED. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|