| Plan Review Notes For Permit 02011248 |
| Permit Number |
02011248 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-09-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) ONLY THE FIXTURES WITHIN THE BATHROOM | | | GROUP SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF | | | THE WET VENT. 909.1 - THE LAUNDRY TRAY | | | SHALL NOT DRAIN THROUGH THE BATHROOM | | | GROUP. | | | 2) SANITARY RISER SHALL REFLECT THE | | | FLOOR PLAN. PLEASE SEE RED LINE CORRECT- | | | IONS ON REVISION SHEET AND MAKE NECESS- | | | ARY CHANGES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|