| Plan Review Notes For Permit 02011166 |
| Permit Number |
02011166 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-24 00:00:00 | ****************UNSAT!****************** | | | | | | PLEASE PROVIDE THE A.I.C. RATING AT THE | | | FIRST MEANS OF DISCONNECT,NOT AT THE | | | TRANSFORMER.PLEASE CALCULATE AND | | | RESUBMIT SAME. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | (561) 659-8096 EXT.8392 |
|