| Notes |
| Date |
Text |
| 2002-03-03 00:00:00 | PLUMBING PLAN REVIEW,FBC 2001, DENIED | | | (1) GENERAL NOTES (14) DESIGN IS NOT BY | | | WPB SWIMMING POOL CODE, SEE FBC 2001". | | | SEC 424.2.6 | | | (2) SEC 424.2.6.6.2 SUCTION FITTINGS, | | | CLEANING LINE. | | | (3) SEC 424..2.7.2 SHOW A DETAIL OF MOUN | | | TING AND ANCHORING POOL,SPA EQUIPMENT. | | | (4) 424.2.9 WATER SUPPLY,LOCAL ORDINANCE | | | #2853-95 BACK FLOW PREVENTER REQUIRED ON | | | WATER SERVICE. | | | (5) SEC 424.2.13.2 JOINTS, CONNECTIONS, | | | PURPLE PRIMER REQUIRED ON PVC PIPING. | | | FBC-2001 PLUMBING SEC605.21 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|