| Plan Review Notes For Permit 02011130 |
| Permit Number |
02011130 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-30 00:00:00 | ********************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT NO GROUNDING | | | ELECTRODE WAS SHOWN FOR DETACHED BLDG. | | | PER 250-32 | | | ALSO SHOW EQUIPMENT GROUNDING CONDUCTOR. | | | | | | 2)NOTE: PLEASE CLARIFY PANEL "A" ON | | | RISER DIAGRAM AND PANEL SCHEDULE SHOWS | | | "B"? | | | | | | 3)NOTE: PLEASE SHOW GARAGE OUTLETS TO | | | BE GFI/GFI PROTECTED PER 210-8 | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|