| Plan Review Notes For Permit 02011118 |
| Permit Number |
02011118 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-06 00:00:00 | A) PLEASE CLEARLY INDICATE ON THE PLANS | | | THAT NO PENETRATIONS INTO THE REQUIRED | | | EXIT STAIRS WILL OCCUR WITH NEW | | | EQUIPMENT. NO PENETRATIONS WILL BE | | | ALLOWED INTO THE STAIRWELLS. THE PLAN | | | SEEMS TO SUGGEST PENETRATIONS INTO | | | THE STAIRS. | | | B) WRONG LIFE SAFETY CODE REFERENCED. | | | SHOULD READ THE 2000 EDITION OF THE | | | LIFE SAFETY CODE NOT THE 1990 EDITION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|