Plan Review Notes
Plan Review Notes For Permit 02011116
Permit Number 02011116
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-02 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) SHT AF-1 GREASE TRAP. PLEASE CONTACT
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 (561) 837-4074 FOR GREASE TRAP SIZE.
 WASTE ORD. #2938-96
 2) SEPARATE PERMIT REQUIRED FOR GREASE
 TRAP. PROVIDER OF GREASE TRAP NOT PLUMB-
 ING CONTRACTOR TO APPLY FOR PERMIT.
 3) SHT PG-1 DRAIN ISOMETRIC/DRAIN LAYOUT
 HUB DRAINS NOT APPROVED. ALL INDIRECT
 WASTE TO DRAIN TO FLOOR SINKS. SPC SEC
 804.1 & 804.5
 4) SHT PG-1 FLOOR DRAIN WITH TRAP PRIMER
 REQUIRED IN PUBLIC TOILET ROOM. SPC SEC
 409.4.1.1.
 5) BACKFLOW REQUIRED ON WATER SERVICE.
 6) SHT AF-1 PLEASE SHOW CLEAR FLOOR
 SPACE AND TURNING RADIUS IN PLUBLC REST
 ROOM.
 7) LETTER FROM DEPT. OF BUSINESS AND PRO
 FESSIONAL REGULATION STATES IN NOTE #2
 NO SEATING, TAKE OUT ONLY. PLANS STATE
 "SALES - SEATING AREA" AND SHOW SEATING.
 PLEASE CLARIFY.
 8) SEPARATE GAS PERMIT REQUIRED. SEE
 SUBSECTIONS FOR GAS PERMIT APPLICATION
 REQUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 3. TYPE OF GAS, (LP OR NATURAL)
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE STANDARD GAS CODE SEC. 305.4(I).
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 9) PLANS SUBMITTED FOR PLAN REVIEW DO
 NOT HAVE DBPR DIV. OF HOTELS AND RESTUR-
 ANTS APPLICATION ATTACHED NOR ARE THE
 PLANS STAMPED "FOOD SERVICE PLAN APPROV-
 ED"PLEASE SUBMIT STAMPED PLANS WITH
 PLAN REVIEW APPLICATION FROM DIV. OF
 HOTELS AND RESTURANTS
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377