| Plan Review Notes For Permit 02011043 |
| Permit Number |
02011043 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-27 00:00:00 | | | | PROVISO: | | | | | | PRIOR TO INSPECTION PLEASE PROVIDE | | | MANUAL J CALCULATIONS TO MATCH ENERGY | | | CALCULATIONS.PLANS & ENERGY CALCS | | | COINCIDE BUT THE MANUAL J'S DO NOT. | | | | | | PLEASE NOTE, AREAS WITH 300 CFM OR | | | GREATER REQUIRE RETURN AIR FROM THAT | | | AREA. | | | | | | FOUR PLANS SUBMITTED WITH THIS | | | RESUBMITTAL.PLEASE REMOVE OLD PLANS | | | FROM APPROVED SET. | | | | | | THIS APPROVAL IS FOR THE HVAC ONLY. | | | ADDITIONAL INFORMATION REQUIRED FOR THE | | | FIRE PLACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|