Plan Review Notes
Plan Review Notes For Permit 02011043
Permit Number 02011043
Review Stop R
Sequence Number 1
Notes
Date Text
2002-02-21 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) NO FOUNDATION IS SHOWN ON A-2 FOR THE
 WING WALLS THAT EXTEND FROM THE GARAGE
 AT THE FRONT ELEVATION.
  
 4) THE DOTTED LINE INDICATING THE EDGE
 OF THE F3 FOOTING IS MISSING BETWEEN THE
 GARAGE AND BEDROOM #2. (A-2)
  
 5) THE STEEL COLUMNS AT THE FRONT ENTRY
 HAVE NO TAG MARK TO TIE THEM TO THE
 COLUMN SCHEDULE. (A-2)
  
 6) THE HEAD DETAIL FOR THE SLIDING GLASS
 DOOR BUCKS (A-7) DOES NOT INDICATE THE
 FASTNERS, SPACING, ETC. FOR ATTACHING
 THE 1X4 BUCK.
  
 7) PROVIDE AT LEAST ONE FULL BATHROOM
 WITH A DOOR THAT HAS A 29 INCH CLEAR
 OPENING.
  
 8) SAFETY GLASS IS REQUIRED IN THE
 WINDOW OF BED ROOM #4 THAT IS WITHIN 2'
 OF THE BATHROOM DOOR. 97SBC 2405.2.1 (3)
  
 9) THE ATTIC ACCESS OPENINGS SHALL NOT
 BE LESS THAN 22"X 36" PER 97SBC 2309.6.
  
 10) PROVIDE LISTING INFORMATION AND
 MANUFACTURERS SPECIFICATIONS FOR THE
 GAS GRILL. A SEPARATE PERMIT IS REQUIRED
 FOR GAS.
  
 11) PROVIDE FRAMING DETAILS FOR ARCH
 OPENINGS.
  
 12) INDICATE ROOF NAILING SCHEDULE THAT
 COMPLIES WITH THE CITY OF WPB AMENDMENTS
 TO THE 97SBC. 8D COMMOMON NAILS 6" O.C.
 AT EDGES AND INTERMEDIATE FOR ZONES 1 &
 2 AND 4" O.C. AT EDGES AND 6" O.C.
 INTERMEDIATE FOR ZONE 3.
  
 13) EGRESS WINDOW IS REQUIRED IN THE
 LIBRARY, WHICH COULD BE USED AS A
 SLEEPING ROOM. 97SBC 1005.4
  
 14) THE TRUSS ANCHOR SCHEDULE ON A-6
 STATES THAT TAPR222 WITH 10-10D NAILS IS
 RATED FOR 1485# OF UPLIFT. HOWEVER,THE
 2001 USP CATALOG REQUIRES 14-10D NAILS.
 PLEASE CORRECT.
  
 15) PROVIDE A LETTER FROM USP FOR
 INSTALLATION OF TRUSS CONNECTORS STRAPS
 SPACED CLOSER THAN 8" INDICATING THE
 REDUCED LOAD VALUES.
  
 16) THE USP CATALOG DOES NOT LIST AN
 RT24. PLEASE CLARIFY. RT20,RT24F AND
 RT24T ARE LISTED.
  
 17) THE PLATE TO STUD CONNECTORS FOR THE
 INTERIOR BEARING PARTITIONS ON DETAIL C
 ON A-9 ARE GIVEN AS (USP) TPP. THESE ARE
 MENDING PLATES IN THE USP CATALOG AND
 NOT INTENDED FOR STRUCTURAL USE. PLEASE
 INDICATE APPROPRIATE CONNECTORS, SUCH AS
 USP SPT66 OR TP6X.
  
 18) WALL SECTION 1 ON A-7 SHOULD
 INDICATE THAT THE BOTTOM OF THE FOOTING
 SHALL BE A MINIMUM OF 12" BELOW GRADE
 AND THE FINISH FLOOR SHALL BE A MINIMUM
 OF 4" ABOVE FINISH GRADE. 97SBC 1804.1.3
 & CITY OF WPB AMENDMENTS 1804.1.9.
  
 19)PLEASE INDICATE (CIRCLE) ON THE
 PRODUCT APPROVAL THE TYPE OF
 FASTENERS THAT WILL BE USED TO ATTACH
 STORM PANELS.
  
 20) THE PRODUCT EVALUATION FROM SBCCI
 # 9652 HAS BEEN REPLACED BY # 9652A. THE
 16' X 8' GARAGE DOOR THAT IS INDICATED
 ON THE EVALUATION THAT WAS REPLACED IS
 NO LONGER LISTED ON THE UPDATED REPORT.
 PLEASE INDICATE WHICH DOOR WILL BE USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202