| 2002-02-21 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) NO FOUNDATION IS SHOWN ON A-2 FOR THE |
| | WING WALLS THAT EXTEND FROM THE GARAGE |
| | AT THE FRONT ELEVATION. |
| | |
| | 4) THE DOTTED LINE INDICATING THE EDGE |
| | OF THE F3 FOOTING IS MISSING BETWEEN THE |
| | GARAGE AND BEDROOM #2. (A-2) |
| | |
| | 5) THE STEEL COLUMNS AT THE FRONT ENTRY |
| | HAVE NO TAG MARK TO TIE THEM TO THE |
| | COLUMN SCHEDULE. (A-2) |
| | |
| | 6) THE HEAD DETAIL FOR THE SLIDING GLASS |
| | DOOR BUCKS (A-7) DOES NOT INDICATE THE |
| | FASTNERS, SPACING, ETC. FOR ATTACHING |
| | THE 1X4 BUCK. |
| | |
| | 7) PROVIDE AT LEAST ONE FULL BATHROOM |
| | WITH A DOOR THAT HAS A 29 INCH CLEAR |
| | OPENING. |
| | |
| | 8) SAFETY GLASS IS REQUIRED IN THE |
| | WINDOW OF BED ROOM #4 THAT IS WITHIN 2' |
| | OF THE BATHROOM DOOR. 97SBC 2405.2.1 (3) |
| | |
| | 9) THE ATTIC ACCESS OPENINGS SHALL NOT |
| | BE LESS THAN 22"X 36" PER 97SBC 2309.6. |
| | |
| | 10) PROVIDE LISTING INFORMATION AND |
| | MANUFACTURERS SPECIFICATIONS FOR THE |
| | GAS GRILL. A SEPARATE PERMIT IS REQUIRED |
| | FOR GAS. |
| | |
| | 11) PROVIDE FRAMING DETAILS FOR ARCH |
| | OPENINGS. |
| | |
| | 12) INDICATE ROOF NAILING SCHEDULE THAT |
| | COMPLIES WITH THE CITY OF WPB AMENDMENTS |
| | TO THE 97SBC. 8D COMMOMON NAILS 6" O.C. |
| | AT EDGES AND INTERMEDIATE FOR ZONES 1 & |
| | 2 AND 4" O.C. AT EDGES AND 6" O.C. |
| | INTERMEDIATE FOR ZONE 3. |
| | |
| | 13) EGRESS WINDOW IS REQUIRED IN THE |
| | LIBRARY, WHICH COULD BE USED AS A |
| | SLEEPING ROOM. 97SBC 1005.4 |
| | |
| | 14) THE TRUSS ANCHOR SCHEDULE ON A-6 |
| | STATES THAT TAPR222 WITH 10-10D NAILS IS |
| | RATED FOR 1485# OF UPLIFT. HOWEVER,THE |
| | 2001 USP CATALOG REQUIRES 14-10D NAILS. |
| | PLEASE CORRECT. |
| | |
| | 15) PROVIDE A LETTER FROM USP FOR |
| | INSTALLATION OF TRUSS CONNECTORS STRAPS |
| | SPACED CLOSER THAN 8" INDICATING THE |
| | REDUCED LOAD VALUES. |
| | |
| | 16) THE USP CATALOG DOES NOT LIST AN |
| | RT24. PLEASE CLARIFY. RT20,RT24F AND |
| | RT24T ARE LISTED. |
| | |
| | 17) THE PLATE TO STUD CONNECTORS FOR THE |
| | INTERIOR BEARING PARTITIONS ON DETAIL C |
| | ON A-9 ARE GIVEN AS (USP) TPP. THESE ARE |
| | MENDING PLATES IN THE USP CATALOG AND |
| | NOT INTENDED FOR STRUCTURAL USE. PLEASE |
| | INDICATE APPROPRIATE CONNECTORS, SUCH AS |
| | USP SPT66 OR TP6X. |
| | |
| | 18) WALL SECTION 1 ON A-7 SHOULD |
| | INDICATE THAT THE BOTTOM OF THE FOOTING |
| | SHALL BE A MINIMUM OF 12" BELOW GRADE |
| | AND THE FINISH FLOOR SHALL BE A MINIMUM |
| | OF 4" ABOVE FINISH GRADE. 97SBC 1804.1.3 |
| | & CITY OF WPB AMENDMENTS 1804.1.9. |
| | |
| | 19)PLEASE INDICATE (CIRCLE) ON THE |
| | PRODUCT APPROVAL THE TYPE OF |
| | FASTENERS THAT WILL BE USED TO ATTACH |
| | STORM PANELS. |
| | |
| | 20) THE PRODUCT EVALUATION FROM SBCCI |
| | # 9652 HAS BEEN REPLACED BY # 9652A. THE |
| | 16' X 8' GARAGE DOOR THAT IS INDICATED |
| | ON THE EVALUATION THAT WAS REPLACED IS |
| | NO LONGER LISTED ON THE UPDATED REPORT. |
| | PLEASE INDICATE WHICH DOOR WILL BE USED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |