Plan Review Notes
Plan Review Notes For Permit 02011041
Permit Number 02011041
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-04-09 00:00:00A) NO FIRE HYDRANTS SHOWN ON SITE PLAN.
 ONLY ONE HYDRANT IS SHOWN ON THE
 CONCEPTUAL PAVING AND DRAINAGE PLAN.
 PLEASE INDICATE ALL FIRE HYDRANT
 LOCATIONS WITHIN THE VICINITY OF THE
 STORE.
 B) PLEASE INDICATE THE LOCATION OF THE
 FIRE DEPARTMENT CONNECTION FOR THE
 FIRE SPRINKLER SYSTEM. THIS DEVICE
 MUST BE LOCATED WITHIN 150 FEET OF
 A FIRE HYDRANT.
 C) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED.
 D) NOT ALL PREVIOUS PLAN REVIEW COMMENTS
 HAVE BEEN ADDRESSED. PLEASE REVIEW
 INFORMATION AND MAKE THE APPROPRIATE
 COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910