| Plan Review Notes For Permit 02011041 |
| Permit Number |
02011041 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-04-09 00:00:00 | A) NO FIRE HYDRANTS SHOWN ON SITE PLAN. | | | ONLY ONE HYDRANT IS SHOWN ON THE | | | CONCEPTUAL PAVING AND DRAINAGE PLAN. | | | PLEASE INDICATE ALL FIRE HYDRANT | | | LOCATIONS WITHIN THE VICINITY OF THE | | | STORE. | | | B) PLEASE INDICATE THE LOCATION OF THE | | | FIRE DEPARTMENT CONNECTION FOR THE | | | FIRE SPRINKLER SYSTEM. THIS DEVICE | | | MUST BE LOCATED WITHIN 150 FEET OF | | | A FIRE HYDRANT. | | | C) NO FIRE SPRINKLER DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED. | | | D) NOT ALL PREVIOUS PLAN REVIEW COMMENTS | | | HAVE BEEN ADDRESSED. PLEASE REVIEW | | | INFORMATION AND MAKE THE APPROPRIATE | | | COMMENTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|