2002-02-06 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SHTS P1.1/P2.1 ITEM #15 & WATER HEAT-
 ER DETAIL, ALL DRIP AND INDIRECT TO AN
 APPROVED RECEPTOR. FUNNEL DRAIN AND
 FLOOR DRAIN NOT APPROVED FOR INDIRECT
 WASTE. PLEASE PROVIDE FLOOR SINK FOR ALL
 INDIRECT WASTE. TRAP PRIMER REQUIRED FOR
 WATER HEATER ROOM.
 2) SHT P1.1 BACKFLOW REQUIRED ON WATER
 SERVICE.
 3) BACKFLOW REQUIRED FOR IRRIGATION.
 PLUMBING CONTRACTOR SHALL INSTALL BACK-
 FLOW FOR IRRIGATION CONTRACTOR.
 4) SHT P1.1 PLEASE SUBMIT MANUFACTURE
 INFORMATION FOR TANKLESS WATER HEATERS
 FOR #'S 3 & 16 MOD #'S DCH 10-2/DCH 8-2
 FOR PLAN REVIEW.
 5) SHT P1.1 PLEASE SUBMIT MANUFACTURE
 INFORMATION FOR AUTOMATIC FLUSH SYSTEM
 AT FIXTURE #14 FOR PLAN REVIEW.
 6) SHT A3.1 DETAILS (C-C) & (11), PROVI-
 DE PERMINATE SHIPS LADDER OR PUT W/HEAT-
 ER ON FLOOR TO MAKE HEATER ACCESSIBLE.
 7) SHT P2.1 ELECT. WATER HEATER DETAIL,
 DIELECTRIC UNIONS NOT APPROVED FOR WATER
 PIPING. (GAS FITTING ONLY).
 8) SHT P2.1 WATER HAMMER DETAIL. LOCATE
 WATER HAMMER ARRESTORS NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT ON TOP AS
 SHOWN. SUBMIT WATER RISER DIAGRAM WITH
 PIPE SIZES SHOWING CORRECT LOCATION OF
 WATER HAMMER ARRESTORS NEAR FIXTURES.
 SEC 604.9
  