| Date |
Text |
| 2002-02-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 |
| | |
| | 1) SHTS P1.1/P2.1 ITEM #15 & WATER HEAT- |
| | ER DETAIL, ALL DRIP AND INDIRECT TO AN |
| | APPROVED RECEPTOR. FUNNEL DRAIN AND |
| | FLOOR DRAIN NOT APPROVED FOR INDIRECT |
| | WASTE. PLEASE PROVIDE FLOOR SINK FOR ALL |
| | INDIRECT WASTE. TRAP PRIMER REQUIRED FOR |
| | WATER HEATER ROOM. |
| | 2) SHT P1.1 BACKFLOW REQUIRED ON WATER |
| | SERVICE. |
| | 3) BACKFLOW REQUIRED FOR IRRIGATION. |
| | PLUMBING CONTRACTOR SHALL INSTALL BACK- |
| | FLOW FOR IRRIGATION CONTRACTOR. |
| | 4) SHT P1.1 PLEASE SUBMIT MANUFACTURE |
| | INFORMATION FOR TANKLESS WATER HEATERS |
| | FOR #'S 3 & 16 MOD #'S DCH 10-2/DCH 8-2 |
| | FOR PLAN REVIEW. |
| | 5) SHT P1.1 PLEASE SUBMIT MANUFACTURE |
| | INFORMATION FOR AUTOMATIC FLUSH SYSTEM |
| | AT FIXTURE #14 FOR PLAN REVIEW. |
| | 6) SHT A3.1 DETAILS (C-C) & (11), PROVI- |
| | DE PERMINATE SHIPS LADDER OR PUT W/HEAT- |
| | ER ON FLOOR TO MAKE HEATER ACCESSIBLE. |
| | 7) SHT P2.1 ELECT. WATER HEATER DETAIL, |
| | DIELECTRIC UNIONS NOT APPROVED FOR WATER |
| | PIPING. (GAS FITTING ONLY). |
| | 8) SHT P2.1 WATER HAMMER DETAIL. LOCATE |
| | WATER HAMMER ARRESTORS NEAR THE FIXTURE |
| | IN AN "EFFECTIVE RANGE" NOT ON TOP AS |
| | SHOWN. SUBMIT WATER RISER DIAGRAM WITH |
| | PIPE SIZES SHOWING CORRECT LOCATION OF |
| | WATER HAMMER ARRESTORS NEAR FIXTURES. |
| | SEC 604.9 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |