2002-02-14 00:00:00*******************DENIED***************
  
 APPLICABLE CODE - 2001 FLORIDA BUILDING
 CODE, MECHANICAL
  
  
 1.INDICATE HOW EQUIPMENT ON THE ROOF
 IS TO BE ACCESSED FOR SERVICE AND
 MAINTENANCE.AS PER 306.5 AN
 APPROVED PERMANENT MEANS OF ACCESS
 IS REQUIRED FOR EQUIPMENT INSTALLED
 ON ROOFS AT A HEIGHT EXCEEDING 16'.
  
 PLEASE NOTE, ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30".
  
 SEPARATE PERMITS REQUIRED FOR WALK-IN
 COOLERS AND FREEZER.PLEASE PROVIDE
 PLANS AND MANUFACTURER SUBMITTAL DATA
 WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.