| 2002-02-08 00:00:00 | 1) PLEASE BE ADVISED THAT MERCANTILE |
| | OCCUPANCIES ARE LOCATED IN CHAPTER 36 |
| | OF THE FLORIDA FIRE PREVENTION CODE, |
| | 2000 LIFE SAFETY CODE. THE REFERENCES |
| | TO CHAPTER 24 ARE NO LONGER APPLICABLE. |
| | 2) HOW IS EXIT DISCHARGE ACCOMPLISHED |
| | THRU THE EXTERIOR TOTE STORAGE. |
| | 3) THE FIRE SPRINKLER SYSTEM RISER |
| | DOES NOT INDICATE THE LOCATION OF |
| | THE REQUIRED FIRE DEPARTMENT CONNECTION. |
| | PLEASE BE ADVISED THAT THIS DEVICE MUST |
| | BE WITHIN 150 FEET OF A FIRE HYDRANT. |
| | 4) PLEASE PROVIDE COMPLETE FIRE |
| | SPRINKLER DRAWINGS AND HYDRAULIC |
| | CALCULATIONS FOR THE FIRE SPRINKLER |
| | SYSTEM. A SEPARATE PERMIT IS REQUIRED. |
| | 5) PLEASE PROVIDE COMPLETE FIRE ALARM |
| | SYSTEM DRAWINGS. CUT SHEETS, WIRING |
| | DIAGRAM AND BATTERY CALCULATIONS ARE |
| | TO BE PROVIDED. A SEPARATE PERMIT IS |
| | REQUIRED. A REMOTE ANNUNCIATOR APPEARS |
| | TO BE NEEDED. |
| | 6) THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM ARE TO BE MONITORED BY |
| | A LICENSED UL LISTED CENTRAL STATION. |
| | 7) HOW DOES BALER 31B AFFECT EXITING. |
| | 8) ELECTRONIC SWITCHES,CHAIN AND LOCK |
| | ARE REQUIRED ON BACKFLOW DEVICE. |
| | 9) AUTOMATIC SLIDING DOORS TO COMPLY |
| | WITH NFPA 101, THE LIFE SAFETY CODE, |
| | 2000 EDITION, SECTION 7.2.1.9.1. |
| | 10) DIFFERENT NUMBERS ARE PRESENT ON |
| | PAGE L-1 AND A1.1 WITH REGARDS TO |
| | SQUARE FOOTAGE OF BUILDING. PLEASE |
| | CORRECT INFORMATION. |
| | 11) PLEASE INDICATE ALL FIRE HYDRANT |
| | LOCATIONS NEAR THE SITE FOR THE |
| | NEW BUILDING. |
| | 12) PLEASE EXPLAIN WHY TWO DIFFERENT |
| | WALL SYSTEMS EXIST NEAR PHOTO, FOOD |
| | MART AND GENERAL STORAGE AREAS. |
| | 13) TWO TELEPHONE LINES WILL BE REQUIRED |
| | TO MONITOR THE FIRE SPRINKLER AND OR |
| | FIRE ALARM SYSTEMS. SEE NOTE 10 ON |
| | PAGE E1.5. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |