2002-02-08 00:00:001) PLEASE BE ADVISED THAT MERCANTILE
 OCCUPANCIES ARE LOCATED IN CHAPTER 36
 OF THE FLORIDA FIRE PREVENTION CODE,
 2000 LIFE SAFETY CODE. THE REFERENCES
 TO CHAPTER 24 ARE NO LONGER APPLICABLE.
 2) HOW IS EXIT DISCHARGE ACCOMPLISHED
 THRU THE EXTERIOR TOTE STORAGE.
 3) THE FIRE SPRINKLER SYSTEM RISER
 DOES NOT INDICATE THE LOCATION OF
 THE REQUIRED FIRE DEPARTMENT CONNECTION.
 PLEASE BE ADVISED THAT THIS DEVICE MUST
 BE WITHIN 150 FEET OF A FIRE HYDRANT.
 4) PLEASE PROVIDE COMPLETE FIRE
 SPRINKLER DRAWINGS AND HYDRAULIC
 CALCULATIONS FOR THE FIRE SPRINKLER
 SYSTEM. A SEPARATE PERMIT IS REQUIRED.
 5) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM DRAWINGS. CUT SHEETS, WIRING
 DIAGRAM AND BATTERY CALCULATIONS ARE
 TO BE PROVIDED. A SEPARATE PERMIT IS
 REQUIRED. A REMOTE ANNUNCIATOR APPEARS
 TO BE NEEDED.
 6) THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM ARE TO BE MONITORED BY
 A LICENSED UL LISTED CENTRAL STATION.
 7) HOW DOES BALER 31B AFFECT EXITING.
 8) ELECTRONIC SWITCHES,CHAIN AND LOCK
 ARE REQUIRED ON BACKFLOW DEVICE.
 9) AUTOMATIC SLIDING DOORS TO COMPLY
 WITH NFPA 101, THE LIFE SAFETY CODE,
 2000 EDITION, SECTION 7.2.1.9.1.
 10) DIFFERENT NUMBERS ARE PRESENT ON
 PAGE L-1 AND A1.1 WITH REGARDS TO
 SQUARE FOOTAGE OF BUILDING. PLEASE
 CORRECT INFORMATION.
 11) PLEASE INDICATE ALL FIRE HYDRANT
 LOCATIONS NEAR THE SITE FOR THE
 NEW BUILDING.
 12) PLEASE EXPLAIN WHY TWO DIFFERENT
 WALL SYSTEMS EXIST NEAR PHOTO, FOOD
 MART AND GENERAL STORAGE AREAS.
 13) TWO TELEPHONE LINES WILL BE REQUIRED
 TO MONITOR THE FIRE SPRINKLER AND OR
 FIRE ALARM SYSTEMS. SEE NOTE 10 ON
 PAGE E1.5.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910