2002-02-08 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE CLARIFY NOT ON E 1.2
 NOTE #6, PLEASE SEE 6'6" TO TOP OF MAIN?
 PLEASE SEE MDP SHOWN ON E 3.2 MAIN SHOWN
 AT BOTTOM OF SWITCH GEAR?
  
 2)NOTE: PLEASE CLARFIY VOLTAGE OF
 SERVICE. 3.2 MDP SHOWS 120/240. PLEASE
 SEE OTHERSHEET,2.1,3.1 ECT OTHER VOLTAGE
 -S SHOWN AT 120/208.PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372