Plan Review Notes
Plan Review Notes For Permit 02011041
Permit Number 02011041
Review Stop B
Sequence Number 1
Notes
Date Text
2002-02-14 00:00:00PLAN REVIEW FOR 2001 FBC:
 ONE STORY, 13,400 +/- SQUARE FEET, GROUP
 M OCCUPANCY, TYPE V, FS CONSTRUCTION
 SHOWN.
  
 THE FIRE PROTECTION PLANS, (SPRINKLERS,
 ALARM, ETC.) MUST BE INCLUDED WITH THE
 PERMIT APPLICATION.SEE FBC 104.3.1.1
 #5
  
 THE PLANS SHOULD CITE THE SPECIFIC
 EDITIONS OF THE CODES AND STANDARDS
 USED IN THE DESIGN.THE FL STATE FIRE
 MARSHALL'S OFFICE HAS INVOKED NFPA
 13-99 AND THE 2000 LIFE SAFETY CODE
 (NFPA 101), AMONGST OTHERS.SEE FBC
 3501 FOR OTHERS.
  
 STRUCTURAL, SPECIFY THE WIND DESIGN
 USED1606.2 OR ASCE 7-98. SHOW THE WIND
 PRESSURES FOR THE WALLS, (COMPONENTS
 AND CLADDING), TO BE USED FOR WINDOWS
 AND DOORS.
  
 INCLUDE A DOOR AND WINDOW SCHEDULE WITH
 THE PERMIT PLANS.
  
 DETAIL 7/S7 IN REFERENCE TO SECTION 1/S7
 IS NOT CLEAR AS TO ITS IMPLEMENTATION.
 HOW ARE THE METAL STUDS FASTENED TO THE
 DOUBLE WOOD PLATE?HOW IS THE NELSON
 STUD CONNECTED TO THE WOOD PLATE?WHY
 IS A TRUSS REFERENCED?
  
 SHEET A2.3 DEPICTS THE EXTERIOR CANOPY,
 SHOW THE DRAFTSTOPPING REQUIRED BY FBC
 2305.2.4.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY FOR THE CITY, THE
 PERMIT PLANS STAMPED BY THAT OFFICE AND
 A COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.