| 2002-07-15 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 2/6/02: |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SBC* 104.2STOREFRONT.THIS COMMENT |
| | HAS NOT BEEN ADDRESSED.SEE PREVIOUS |
| | REVIEW.THE 'PROJECT SUMMARY' STILL |
| | CONTRADICTS THE 'DEMOLITION KEY'. AMEND |
| | THE PLANS TO CLARIFY THE SCOPE OF WORK. |
| | |
| | 3) SBC* 104.2'NEW SLAB'.THIS COMMENT |
| | HAS NOT BEEN ADDRESSED.SEE PREVIOUS |
| | REVIEW.THE 'PROJECT SUMMARY' STILL |
| | REFERS TO INSTALLATION OF A NEW SLAB ON |
| | GRADE.SHEETS A1.1 AND A1.3 DO NOT SHOW |
| | ANY DETAILS OF THIS.AMEND THE PLANS TO |
| | CLARIFY THE SCOPE OF WORK. |
| | |
| | 4) SBC* 104.2CT SCAN, LEAD SHIELDING. |
| | THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SEE PREVIOUS REVIEW.WHILST THE CT SCAN |
| | ROOM WALLS HAVE BEEN DESIGNED WITH LEAD |
| | SHIELDING, NO LEAD SHIELDING HAS BEEN |
| | SPECIFIED FOR THE WALL IN FRONT OF THE |
| | STOREFRONT GLAZING.SUBMIT DETAILS FROM |
| | THE CT SCANNER SUPPLIER TO DESCRIBE THE |
| | MANUFACTURER'S SAFETY REQUIREMENTS FOR |
| | THE INSTALLATION SITE. |
| | |
| | 5) FL ACC CODE 4.16.4TOILET GRAB BAR. |
| | THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SEE PREVIOUS REVIEW.THE HEIGHT OF THE |
| | GRAB BAR BEHIND THE W.C. EXCEEDS THE |
| | MAXIMUM ALLOWABLE OF 36" ABOVE FLOOR |
| | LEVEL.AMEND THE PLANS TO SHOW |
| | COMPLIANCE. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |