Plan Review Notes
Plan Review Notes For Permit 02011035
Permit Number 02011035
Review Stop B
Sequence Number 2
Notes
Date Text
2002-07-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 2/6/02:
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2STOREFRONT.THIS COMMENT
 HAS NOT BEEN ADDRESSED.SEE PREVIOUS
 REVIEW.THE 'PROJECT SUMMARY' STILL
 CONTRADICTS THE 'DEMOLITION KEY'. AMEND
 THE PLANS TO CLARIFY THE SCOPE OF WORK.
  
 3) SBC* 104.2'NEW SLAB'.THIS COMMENT
 HAS NOT BEEN ADDRESSED.SEE PREVIOUS
 REVIEW.THE 'PROJECT SUMMARY' STILL
 REFERS TO INSTALLATION OF A NEW SLAB ON
 GRADE.SHEETS A1.1 AND A1.3 DO NOT SHOW
 ANY DETAILS OF THIS.AMEND THE PLANS TO
 CLARIFY THE SCOPE OF WORK.
  
 4) SBC* 104.2CT SCAN, LEAD SHIELDING.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 SEE PREVIOUS REVIEW.WHILST THE CT SCAN
 ROOM WALLS HAVE BEEN DESIGNED WITH LEAD
 SHIELDING, NO LEAD SHIELDING HAS BEEN
 SPECIFIED FOR THE WALL IN FRONT OF THE
 STOREFRONT GLAZING.SUBMIT DETAILS FROM
 THE CT SCANNER SUPPLIER TO DESCRIBE THE
 MANUFACTURER'S SAFETY REQUIREMENTS FOR
 THE INSTALLATION SITE.
  
 5) FL ACC CODE 4.16.4TOILET GRAB BAR.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 SEE PREVIOUS REVIEW.THE HEIGHT OF THE
 GRAB BAR BEHIND THE W.C. EXCEEDS THE
 MAXIMUM ALLOWABLE OF 36" ABOVE FLOOR
 LEVEL.AMEND THE PLANS TO SHOW
 COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499