2002-02-06 00:00:00 
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 INDICATE LOCATION AND TERMINATION OF THE
 CONDENSATE.
  
 UNITS GREATER THAN 3 TON SHALL
 TERMINATE:
  
 - INTO AN APPROVED DRYWELL
 - INTO STORM DRAIN.
 (AS PER COUNTYWIDE AMENDMENTS 1994 SPC
 804.3 #2)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT6 59-8096
 EXT. 8388.