Plan Review Notes
Plan Review Notes For Permit 02011035
Permit Number 02011035
Review Stop B
Sequence Number 1
Notes
Date Text
2002-02-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 THE PLANS MAKE REFERENCE TO THE STANDARD
 BUILDING CODE 1997 AND HAVE THEREFOR
 BEEN REVIEWED FOR COMPLIANCE WITH THAT
 CODE
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2THE PROJECT SUMMARY ON
 SHEET A0.1 REFERS TO THE INSTALLATION OF
 NEW STOREFRONT DOORS & GLAZING.THIS IS
 NOT IN AGREEMENT WITH THE DEMOLITION
 PLAN ON SHEET A1.1 WHICH SHOWS THE
 EXISTING STOREFRONT TO REMAIN.AMEND
 THE PLANS TO CLARIFY THE SCOPE OF WORK.
  
 3) SBC* 104.2THE PROJECT SUMMARY ON
 SHEET A0.1 REFERS TO THE INSTALLATION OF
 A NEW SLAB ON GRADE.SHEETS A1.1 & A2.1
 DO NOT SHOW ANY DETAILS OF THIS.AMEND
 THE PLANS TO CLARIFY THE SCOPE OF WORK.
  
 4) SBC* 104.2THE CT SCAN ROOM HAS LEAD
 SHIELDING IN THE WALLS, YET THERE IS NO
 PROTECTION SPECIFIED AT THE EXISTING
 EXTERIOR GLAZED WALL.SUBMIT DETAILS
 FROM THE CT SCANNER SUPPLIER TO
 DESCRIBE THE MANUFACTURER'S SAFETY
 REQUIREMENTS FOR THE INSTALLATION SITE.
  
 5) FL ACC CODE 4.16.4THE HEIGHT OF THE
 GRAB BAR BEHIND THE W.C. EXCEEDS THE
 MAXIMUM ALLOWABLE OF 36" ABOVE FLOOR
 LEVEL.AMEND THE PLANS TO SHOW
 COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499