| 2002-01-22 00:00:00 | | | | CLARIFY DUCT SIZE GOING DOWN TO 1ST FL, | | | PLANS SHOW 2 10 X 6 SIDEWALL BACK TO | | | BACK?SIZE OF DUCT PRIOR TO | | | SIDEWALL..9 X 9 AFTER. | | | | | | LOCATION OF AHU?CLOSET OR ATTIC? | | | | | | ATTIC REQUIRES 22" BY 36" CONTINUOUS | | | FROM THE OPENING TO THE EQUIPMENT & ITS | | | CONTROLS. | | | | | | DUCT SIZE IN THE APT.ARE THEY ALL THE | | | SAME 46"& 1 4"? |
|