Plan Review Notes
Plan Review Notes For Permit 02010870
Permit Number 02010870
Review Stop M
Sequence Number 1
Notes
Date Text
2002-01-22 00:00:00 
 CLARIFY DUCT SIZE GOING DOWN TO 1ST FL,
 PLANS SHOW 2 10 X 6 SIDEWALL BACK TO
 BACK?SIZE OF DUCT PRIOR TO
 SIDEWALL..9 X 9 AFTER.
  
 LOCATION OF AHU?CLOSET OR ATTIC?
  
 ATTIC REQUIRES 22" BY 36" CONTINUOUS
 FROM THE OPENING TO THE EQUIPMENT & ITS
 CONTROLS.
  
 DUCT SIZE IN THE APT.ARE THEY ALL THE
 SAME 46"& 1 4"?


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved