Plan Review Notes
Plan Review Notes For Permit 02010859
Permit Number 02010859
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-02 00:00:00PLUMBING PLAN REVIEW, DENIED
 (1) COMPLY WITH FBC POOLS & SPAS 2001
 SEC.424.2.6.6 ENTRAPMENT PROTECTION FOR
 SUCTIONS INLETS.
 A MINIMUM OF 2 SUCTION INLETS SHALL BE
 PROVIDED FOR EA PUMP IN THE SUCTION
 INLET SYSTEM, SEPERATED BY A MINIMUM OF
 3' OR LOCATED ON TWO DIFFERENT PLANES,
 ONE ON THE BOTTM AND ONE ON THE VERTICAL
 WALL, OR ONE EA ON TWO SEPERATE VERTICAL
 WALLS. PLUMBED SUCH THAT WATER IS DRAWN
 THROUGH THEM SIMULTANEOUSLY THROUGH A
 COMMON LINE TO THE PUMP.
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096X8233