| Plan Review Notes For Permit 02010756 |
| Permit Number |
02010756 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-04-24 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT P0.1 PLUMBING FIXTURE SCHEDULE. | | | FROM PREVIOUS REVIEW - SUBMITTAL FOR 1WH | | | AND 1WH-1 NOT APPROVED. DADE COUNTY | | | APPROVAL NOT ACCEPTABLE. IT IS ALSO | | | OUT OF DATE AS OF 7-18-99 SO IT IS NOT | | | VALID. PLEASE SUBMIT MANUFACTURE INFOR- | | | MATION FOR THESE WATER HEATERS. | | | 2) SHTS P2.1 AND P2.2, PLEASE SUBMIT DE- | | | TAIL FOR SOAKAGE PIT FOR APPROVAL. | | | 3) PREVIOUS REVIEW COMMENT #6 NOT REPLY | | | NOT SHOWN ON PLAN AS INDICATED. SHT A3.1 | | | DETAIL D/A1.2 SHOWS NO MEASURMENTS FOR | | | URNAL HEIGHT. PLEASE INDICATE HEIGHT FOR | | | REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|