Plan Review Notes
Plan Review Notes For Permit 02010756
Permit Number 02010756
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-01 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT PO.1 CONDENSATE TRAP DETAIL, VENT
 SHALL NOT TERMINATE IN MECHANICAL ROOM
 THAT IS USED AS A PLENUM.
 2) CONDENSATE SHALL BE FULL SIZE FROM
 AHU.
 3) SHT PO.1 PLUMBING FIXTURE SCHEDULE,
 1WH & 1WH-1 PLEASE SUBMIT MANUFACTURE
 CUT SHEET TO CHECK FOR A LISTING APPROV-
 AL.
 4) SHTS P2.1 & P5.1 FUNNEL DRAIN NOT
 APPROVED. CONDENSATE SHALL NOT DRAIN TO
 SANITARY, MUST RUN TO CONDENSATE AT WET
 COLUMN, OUTSIDE TO STORM OR TO A DRYWELL
 OUTSIDE BLDG. SAME FOR SECOND FLOOR COND
 5) SHT P2.2 PER SPC TABLE 407 TWO DRINK-
 ING FOUNTAIN ARE REQUIRED FOR THE SECOND
 FLOOR. ONLY ONE SHOWN.
 6) SHT 3.1 DETAILS B/A1.1 & D/A1.1,
 URNAL TO BE 17" AFF MAX TO LIP. PLEASE
 SHOW ON PLAN.
 SHT P5.1 SANITARY ISOMETRIC, WASTE FOR
 SECOND FLOOR SHALL DRAIN INTO 5" SANT.
 WASTE STACK NOT INTO BRANCH LINE FOR
 FIRST FLOOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377