2002-02-04 00:00:00********************DENIED**************
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.INDICATE SIZE OF DUCT FOR THE BRANCH
 LINES.
  
 2.DUCTS PENETRATING PARTITIONS OR
 WALLS WITH A FIRE RESISTANCE RATING
 OF 1 HOUR OR MORE REQUIRE FIRE
 DAMPERS AS PER 1997 SMC 610.1.2.
  
 IN THE EVENT DUCTS FALL UNDER THE
 EXCEPTION (1997 SMC 610.1.3), SHOW
 COMPLIANCE WITH SUB PARAGRAPH #3,
 ITEMS 1 THROUGH 4.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/
 STROBE IN NORMALLY OCCUPIED AREAS AS
 PER NFPA 90A 4-4.4.3.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 IS ALSO REQUIRED FOR UNITS UNDER
 2,000 CFM IF SERVING AN AREA OF
 EGRESS AS PER 1997 SMC 406.2.
 (AHU-INS-6)
  
 4.AIR BALANCE SCHEDULE - THE NOTE AT
 THE BOTTOM OF THE SCHEDULE STATES
 "PROVIDE RELIEF ON SHEET M2.2",
 RELIEF IS INDICATED ON PLAN SHEET
 M2.1.
  
 5.AIR SYSTEM SIZING SHEETS - THE
 FOLLOWING AHU DO NOT MATCH THE
 EQUIPMENT SCHEDULE ON SHEET M0.1.
  
 AHU-INS-3, 7, 9 & VAN-1.
 NO SIZING CALCULATIONS FOR
 AHU-INS-11.
  