2002-01-30 00:00:00***************** UNSAT ***************
  
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW THE LOAD CALCULATIONS PER,220-3,
 220-10,220-11,220-13 AND ALL CONTINUOUS
 LOADS AT 125% TO VERFIY PANEL SIZING
 AND OCP.215-3,230-42 .
 LARGEST MOTOR LOAD AT 125%
  
 PLEASE NOTE THAT PER FIRE PLAN REVIEW
 THERE MAY ALSO BE SOME CHANGES TO THE
 ELECTRICAL PLANS. PLEASE CLARFIY ANY
 LOW VOLTAGE DEVICES THAT MAY BE INCLUDED
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  