| Plan Review Notes For Permit 02010756 |
| Permit Number |
02010756 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-30 00:00:00 | ***************** UNSAT *************** | | | | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | SHOW THE LOAD CALCULATIONS PER,220-3, | | | 220-10,220-11,220-13 AND ALL CONTINUOUS | | | LOADS AT 125% TO VERFIY PANEL SIZING | | | AND OCP.215-3,230-42 . | | | LARGEST MOTOR LOAD AT 125% | | | | | | PLEASE NOTE THAT PER FIRE PLAN REVIEW | | | THERE MAY ALSO BE SOME CHANGES TO THE | | | ELECTRICAL PLANS. PLEASE CLARFIY ANY | | | LOW VOLTAGE DEVICES THAT MAY BE INCLUDED | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|