Plan Review Notes
Plan Review Notes For Permit 02010651
Permit Number 02010651
Review Stop P
Sequence Number 2
Notes
Date Text
2002-03-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) FROM PREVIOUS REVIEW. PLEASE SUBMIT
 AN EXISTING FLOOR PLAN TO DETERMINE THE
 SCOPE OF REMODELING.
 2) FROM PREVIOUS REVIEW. SEPARATE GAS
 PERMIT REQUIRED. PLEASE SEE ATTACHED GAS
 PERMIT APPLICATION REQUIREMENTS SHEET &
 SUPPLY INFORMATION GAS PLAN REVIEW.
 3) SEPARATE GAS DEMO PERMIT WILL BE RE-
 QUIRED.
 4) FROM PREVIOUS REVIEW. SHT A-8 CONDEN-
 SATE A/C NOTE #15 CONDENSATE TO DRAIN TO
 DRYWELL OR STORM OUTSIDE OF BLDG. CONDEN
 SATE LINE SHALL HAVE A RELIEF VENT NEAR
 BLDG.-THIS #15 HAS BEEN CHANGED AND
 I SEE NO REFERENCE TO CONDENSATE ON THE
 PAGE IN QUESTION. PLEASE SUBMIT A DETAIL
 FOR THE CONDENSATE DRAIN.
 5) FROM PREVIOUS REVIEW. ROOF PLAN.
 PLEASE CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS USING SPC SEC 1108
 AND 1109. INCLUDE 1/2 AREA OF ALL VERTI-
 CAL WALLS. SHOW LOCATIONS FOR PRIMARY
 AND SECONDARY DRAINS AND SHOW DETAILS
 FOR SIZE AND SHOW RISER WITH PIPE SIZES.
 6) FROM PREVIOUS REVIEW. NEW GREASE TRAP
 SHALL HAVE TO BE INSTALLED OUTSIDE OF
 THE BLDG PER CONVERSATION WITH RODNEY
 COMPO. HE INDICATES THAT THE GREASE TRAP
 DOES NOT MEET CODE AND THAT THE BAFFLES
 HAVE BEEN REMOVED. SEPARATE SANITARY AND
 GREASE LINE SHALL BE REQUIRED. PLEASE
 INDICATE SEPARATE LINES WHEN RESUBMITT-
 ING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377