| Date |
Text |
| 2002-03-19 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 - SGC-97 |
| | |
| | 1) FROM PREVIOUS REVIEW. PLEASE SUBMIT |
| | AN EXISTING FLOOR PLAN TO DETERMINE THE |
| | SCOPE OF REMODELING. |
| | 2) FROM PREVIOUS REVIEW. SEPARATE GAS |
| | PERMIT REQUIRED. PLEASE SEE ATTACHED GAS |
| | PERMIT APPLICATION REQUIREMENTS SHEET & |
| | SUPPLY INFORMATION GAS PLAN REVIEW. |
| | 3) SEPARATE GAS DEMO PERMIT WILL BE RE- |
| | QUIRED. |
| | 4) FROM PREVIOUS REVIEW. SHT A-8 CONDEN- |
| | SATE A/C NOTE #15 CONDENSATE TO DRAIN TO |
| | DRYWELL OR STORM OUTSIDE OF BLDG. CONDEN |
| | SATE LINE SHALL HAVE A RELIEF VENT NEAR |
| | BLDG.-THIS #15 HAS BEEN CHANGED AND |
| | I SEE NO REFERENCE TO CONDENSATE ON THE |
| | PAGE IN QUESTION. PLEASE SUBMIT A DETAIL |
| | FOR THE CONDENSATE DRAIN. |
| | 5) FROM PREVIOUS REVIEW. ROOF PLAN. |
| | PLEASE CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS USING SPC SEC 1108 |
| | AND 1109. INCLUDE 1/2 AREA OF ALL VERTI- |
| | CAL WALLS. SHOW LOCATIONS FOR PRIMARY |
| | AND SECONDARY DRAINS AND SHOW DETAILS |
| | FOR SIZE AND SHOW RISER WITH PIPE SIZES. |
| | 6) FROM PREVIOUS REVIEW. NEW GREASE TRAP |
| | SHALL HAVE TO BE INSTALLED OUTSIDE OF |
| | THE BLDG PER CONVERSATION WITH RODNEY |
| | COMPO. HE INDICATES THAT THE GREASE TRAP |
| | DOES NOT MEET CODE AND THAT THE BAFFLES |
| | HAVE BEEN REMOVED. SEPARATE SANITARY AND |
| | GREASE LINE SHALL BE REQUIRED. PLEASE |
| | INDICATE SEPARATE LINES WHEN RESUBMITT- |
| | ING PLANS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |