| 2002-01-30 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FABCB-97 |
| | |
| | 1) PLEASE SUBMIT AN EXISTING FLOOR PLAN |
| | TO DETERMINE SCOPE OF REMODELING. |
| | 2) SEPARATE GAS PERMIT REQUIRED. SEE |
| | ATTACHED GAS PERMIT APPLICATION REQUIRE- |
| | MENT SHEET AND SUPPLY INFORMATION FOR |
| | GAS PLAN REVIEW. |
| | 3) SEPARATE GAS DEMO PERMIT REQUIRED. |
| | 4) ROUTE PLANS TO DEPT. OF BUSINESS REG- |
| | ULATION, HOTEL AND RESTURANT DIV. FOR |
| | PLAN REVIEW BEFORE RESUBMITING TO CITY. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC 101.4.7 |
| | 5) SHT A-5 WATER FILTRATION SYSTEM SHALL |
| | BE NSF APPROVED PER SPC SEC 615.1, 615.2 |
| | SUBMIT MANUFACTURE INFO |
| | 6) SHT A-8 CONDENSATE A/C NOTE #15. CON- |
| | DENSATE TO DRAIN TO DRYWELL OR STORM OUT |
| | SIDE OF BLDG. CONDENSATE DRAIN LINE |
| | SHALL HAVE A RELIEF VENT NEAR BLDG. |
| | PLEASE SHOW DETAILS. |
| | 7) ROOF PLAN, PLEASE SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS |
| | USING SPC SEC 1108, AND 1109. SHOW LOC- |
| | ATIONS FOR PRIMARY AND SECONDARY DRAINS |
| | AND SHOW DETAILS FOR SIZE AND SHOW RISER |
| | WITH PIPE SIZE. |
| | 8) SHT A-3 PLEASE SUBMIT EQUIPMENT SCHED |
| | THAT CORRESPONDS TO EQUIPMENT FLOOR PLAN |
| | 9) RODNEY COMPO, ENVIRONMENTAL COMPLI- |
| | ANCE TO INSPECT GREAS TRAP LOCATED IN |
| | BLDG TO DETERMINE IF MAINTENANCE HAS |
| | BEEN PROVIDED AND IF IT STILL MEETS CODE |
| | IF NOT GREASE TRAP SHALL HAVE TO BE IN- |
| | STALLED OUTSIDE BLDG. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |