Plan Review Notes
Plan Review Notes For Permit 02010651
Permit Number 02010651
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-30 00:00:00DENIED
 REFERENCE: SPC-94 - FABCB-97
  
 1) PLEASE SUBMIT AN EXISTING FLOOR PLAN
 TO DETERMINE SCOPE OF REMODELING.
 2) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED GAS PERMIT APPLICATION REQUIRE-
 MENT SHEET AND SUPPLY INFORMATION FOR
 GAS PLAN REVIEW.
 3) SEPARATE GAS DEMO PERMIT REQUIRED.
 4) ROUTE PLANS TO DEPT. OF BUSINESS REG-
 ULATION, HOTEL AND RESTURANT DIV. FOR
 PLAN REVIEW BEFORE RESUBMITING TO CITY.
 COUNTYWIDE AMENDMENTS TO SPC SEC 101.4.7
 5) SHT A-5 WATER FILTRATION SYSTEM SHALL
 BE NSF APPROVED PER SPC SEC 615.1, 615.2
 SUBMIT MANUFACTURE INFO
 6) SHT A-8 CONDENSATE A/C NOTE #15. CON-
 DENSATE TO DRAIN TO DRYWELL OR STORM OUT
 SIDE OF BLDG. CONDENSATE DRAIN LINE
 SHALL HAVE A RELIEF VENT NEAR BLDG.
 PLEASE SHOW DETAILS.
 7) ROOF PLAN, PLEASE SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 USING SPC SEC 1108, AND 1109. SHOW LOC-
 ATIONS FOR PRIMARY AND SECONDARY DRAINS
 AND SHOW DETAILS FOR SIZE AND SHOW RISER
 WITH PIPE SIZE.
 8) SHT A-3 PLEASE SUBMIT EQUIPMENT SCHED
 THAT CORRESPONDS TO EQUIPMENT FLOOR PLAN
 9) RODNEY COMPO, ENVIRONMENTAL COMPLI-
 ANCE TO INSPECT GREAS TRAP LOCATED IN
 BLDG TO DETERMINE IF MAINTENANCE HAS
 BEEN PROVIDED AND IF IT STILL MEETS CODE
 IF NOT GREASE TRAP SHALL HAVE TO BE IN-
 STALLED OUTSIDE BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377