| Plan Review Notes For Permit 02010651 |
| Permit Number |
02010651 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-24 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE, A-7 SHOWS A NEW | | | 3-PHASE SERICE BEING INSTALLED, RISER | | | ALSO SHOWS THE SAME, EXCEPT FOR METER/ | | | RISER? PLEASE CLARFIY SIZE EXSITING | | | SERVICE ENTRANCE CONDUCTORS. PLEASE | | | CLARIFY EXISTING GROUNDING ELECTRODE | | | LOCATIONS OF ATTACHMENT. | | | | | | 2)NOTE: PLEASE CLARFIY LOCATION OF RECEP | | | FOR ROOFTOP ACCU`S. 210-63. | | | | | | 3)NOTE: PLEASE NOTE OUTLET FOR SIGNAGE | | | PER 600-5. CLARIFY IF EXISTING? | | | | | | 4)NOTE: PLEASE NOTE SPACING FOR SHOW | | | WINDOW OUTLETS PER 210-62. PLEASE | | | CLARFIY IF EXISTING? | | | | | | 5)NOTE: PLEASE NOTE AND OR CLARFIY OCP | | | SHOWN FOR ITEMS ON PANEL SCHEDULE THAT | | | SHOW 25A,35A OCP ON #12 AND #10. PLEASE | | | SEE 310-16, SHOW`S "*" #12/#10WHICH | | | REFERS TO 240-3D. PLEASE NOTE 240-3 | | | LIMITS OCP TO 15/20/30AMPS. | | | | | | 6)NOTE: PLEASE CLARIFY CONDUCTOR SIZES | | | BETWEEN MAIN DISC`S AND PANELS AND | | | EQUIPMENT GROUNIDNG CONDCUTORS PER | | | 250-122. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT8372 |
|