| 2002-03-08 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT REF- | | | LECT FLOOR PLAN, AND DOES NOT MEET CODE | | | REQUIREMENTS. | | | 2) RISER DIAGRAM SHALL REFLECT HOW PIP- | | | ING IS INSTALLED. WASHING MACHINE SHALL | | | BE PIPED FIRST, THEN MASTER BATHROOM | | | SECOND, BATH 2 NEXT, AND THEN KITCHEN | | | LAST. | | | 3) WASHING MACHINE TRAP SHALL BE LOW ON | | | RISER WITH CLEAN OUT AT 4' ABOVE FLOOR. | | | 4) TUB FOR MASTER BATH NOT VENTED. | | | 5) TUB FOR BATH #2 NOT VENTED PROPERLY. | | | 6) PLEASE SUBMIT A SANITARY RISER DIA- | | | GRAM THAT REFLECTS THE FLOOR PLAN AND | | | MEETS THE SPC-94. | | | | | | REVIEW BY KEN STEVENS |
|