| Date |
Text |
| 2002-03-05 00:00:00 | *************BUILDING DENIED************ |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) FORM 600A-97 HAS THE WRONG ADDRESS |
| | AND IS REQUIRED TO BE SIGNED AND DATED |
| | BY THE OWNER/AGENT. PLEASE CORRECT. |
| | |
| | 3) PLEASE CORRECT THE DESIGN DATA ON |
| | SHEET A-1 TO REFER TO THE 1997 STANDARD |
| | BUILDING CODE. |
| | |
| | 4)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL WINDOW MULLIONS |
| | - EXTERIOR DOORS |
| | |
| | 5) THE SITE SPECIFIC PRODUCT APPROVAL |
| | SUBMITTAL FORM FOR THE NORANDEX SINGLE- |
| | HUNG WINDOWS IS REQUIRED TO BE SEALED |
| | AND DATED BY THE ENGINEER CERTIFYING THE |
| | PRODUCT. THE ARCHITECT IS REQUIRED TO |
| | INDICATE DATE IN ADDITION TO SIGNING AND |
| | SEALING THE FORM. |
| | |
| | 6) THE BEDROOM WINDOWS MUST PROVIDE A |
| | MINIMUM NET CLEAR OPENING HEIGHT OF 24" |
| | TO COMPLY WITH 1997 SBC 1005.4. THE |
| | SH 24 WINDOWS TYPICALLY DO NOT PROVIDE |
| | THIS. PLEASE PROVIDE CUT SHEETS FROM THE |
| | WINDOW MANUFACTURER WHICH INDICATE THAT |
| | THE OPENING REQUIREMENTS WILL BE MET. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |