| 2002-02-11 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) PROVIDE SOIL TEST PER SEC. 1804.2.2 |
| | OF CITY AMENDMENTS TO 1997 SBC. |
| | |
| | 4) REVIEW LOCATIONS OF REINFORCED FILLED |
| | CELLS ON SHEETS A-1 AND A-2, SOME DOOR & |
| | WINDOW OPENINGS ARE INDICATED WITHOUT |
| | REINFORCING ON EACH SIDE OF OPENING. THE |
| | 6FT. MAXIMUM O.C. SPACING INDICATED ON |
| | SHEET A-1 APPEARS TO BE EXCEEDED IN |
| | SEVERAL AREAS. |
| | |
| | 5) PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 6) THE DESIGN DATA ON SHEET A-1 SITES |
| | THE 1994 STANDARD BUILDING CODE. THE |
| | CORRECT EDITION IS THE 1997 STANDARD |
| | BUILDING CODE. PLEASE CORRECT. |
| | NOTE: APPLICATIONS FOR PERMITS SUBMITTED |
| | ON OR AFTER MARCH 1, 2002, ARE REQUIRED |
| | TO BE DESIGNED TO COMPLY WITH THE 2001 |
| | SOUTH FLORIDA BUILDING CODE. |
| | |
| | 7) THE TRUSS ANCHORS GIVEN ON SHEET A-1 |
| | DO NOT CLEARLY INDICATED WHICH TRUSSES |
| | THEY WILL BE USED ON. PLEASE CLARIFY. |
| | THE ETA TRUSS ANCHORS INDICATED ON THE |
| | PLANS ARE NO LONGER LISTED IN THE |
| | CURRENT (2002) SIMPSON CATALOG. PLEASE |
| | REVISE PLANS TO SHOW MODEL #S FOR |
| | CURRENTLY LISTED TRUSS ANCHORS. |
| | |
| | 8)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL WINDOW MULLIONS |
| | - EXTERIOR DOORS |
| | |
| | 9) SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND OF THE DESIGN |
| | PROFESSIONAL OF RECORD ON THE PROPER |
| | FORM. SEE ATTACHED. |
| | |
| | 10) BEDROOM WINDOWS MUST COMPLY WITH |
| | 97 SBC 1005.4 FOR EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS. THE MINIMUM NET CLEAR |
| | OPENING HEIGHT IS 24 INCHES AND SH 24 |
| | WINDOWS DO NOT PROVIDE THIS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |