Plan Review Notes
Plan Review Notes For Permit 02010606
Permit Number 02010606
Review Stop B
Sequence Number 1
Notes
Date Text
2002-02-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SBC* 104.1.1A SEPARATE HURRICANE
 MISSILE IMPACT SHUTTER PERMIT IS REQ'D.
  
 3) SBC* 104.2 DETAILS SHALL BE SUBMITTED
 OF THE BEAM, AND IT'S SUPPORTING HEADER
 STUDS, AT THE OPENING THROUGH THE
 EXISTING WALL TO FORM THE NEW BAY WINDOW
  
 4) SBC* 104.2 THE PLANS SHALL BE AMENDED
 TO SHOW WINDOW BUCKS AND HEADERS IN
 ACCORDANCE WITH THE SUBMITTED WINDOW
 PRODUCT APPROVALS.
  
 5) IS THE EXISTING FRONT ENTRANCE DOOR
 TO BE RE-USED?IF NOT, THEN PRODUCT
 APPROVAL IS REQUIRED FOR THE NEW DOOR.
  
 6) SBC* 104.2DETAILS/DESIGN AND
 FASTENING SPECIFICATION FOR THE FOYER
 ROOF TRUSSES SHALL BE SUBMITTED.
  
 7) SBC* 1503.1.2.2 AND SBC 2308.2.2.1
 THE PLANS SHALL BE AMENDED TO SHOW MIN.
 5/8" PLYWOOD (OR EQUIVALENT) SHEATHING
 ON THE NEW WALLS AND FOYER ROOF AND THE
 MEANS OF FASTENING TO THE FRAME/TRUSSES
 IN ACCORDANCE WITH SBC* TABLE 2306.1
  
 8) SBC 1503.1.1THE PLANS SHALL BE
 AMENDED TO ANNOTATE THE ROOF COVERING ON
 THE FOYER ROOF.
  
 9) SBC* 104.2THE PLANS SHALL BE
 AMENDED TO SHOW THE MEANS OF ANCHORING
 THE NEW WOOD FRAMED WALLS TO THE
 FOUNDATIONS AND TO THE EXISTING WALLS.
  
 10) SBC* 104.2THE PLANS SHALL BE
 AMENDED TO SHOW THE MEANS OF TYING THE
 NEW SLAB/FOUNDATIONS TO THE EXISTING.
  
 11) SBC 1804.1.3THE PLANS SHALL BE
 AMENDED TO SHOW THE BASE OF THE NEW
 FOUNDATIONS TO BE AT LEAST 12" BELOW
 FINISH GRADE.
  
 12) SBC* 2304.1.2THE SOIL SHALL BE
 TREATED AGAINST TERMITES PRIOR TO THE
 PLACEMENT OF THE CONCRETE SLABS.
  
 13) SBC* 2304.2.5WOOD SIDING SHALL BE
 AT LEAST 6" CLEAR OF FINISH GRADE EARTH.
  
 14) SBC 2304.3.2ALL WOOD FRAMING AND
 SHEATHING LESS THAN 8" FROM EXPOSED
 EARTH SHALL BE APPROVED NATURALLY
 DURABLE OR PRESSURE TREATED WOOD.
  
 15)FL ENERGY CODE 101.2.2ADDITIONS
 TO EXISTING RESIDENTIAL BUILDINGS SHALL
 COMPLY WITH THE REQUIREMENTS OF EITHER
 METHOD A, B OR C OF CHAPTER 6.
  
 16) FL ENERGY CODE 103.0COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE ENERGY CODE COMPLIANCE FORMS
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499