| Date |
Text |
| 2002-01-14 00:00:00 | ******************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT A TYPICAL |
| | ELECTRICAL RISER DIAGRAM IS SHOWN ON A3 |
| | AND A DIFFERENT RISER IS SHOWN ON A5 |
| | PLEASE NOTE THAT A COMPLETE RISER |
| | DIAGRAM IS NEEDED FOR REVIEW. PLEASE |
| | NOTE GROUPING OF MAIN DISCONNECTS PER |
| | 230-72. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 3)NOTE: PLEASE NOTE THAT NO PANEL |
| | SCHEDULES WERE SUBMITTED FOR UNITS, |
| | CAN BE |
| | TYPICAL. |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 6)NOTE: PLEASE NOTE THAT NO HANDWRITTEN |
| | CHANGES MAY BE ON PLANS UNLESS DONE BY |
| | THE ARCH/ENGINEER OF RECORD AND THEN |
| | EACH INDIVIDUAL CHANGE MUST BE SIGNED |
| | AND DATED.471.025/481.221 |
| | |
| | 7)NOTE: PLEASE NOTE/CLARIFY IF THERE |
| | IS A 2HR SEPARATION OF UNITS IN ORDER |
| | TO HAVE THE SEPARATE SERVICES THAT ARE |
| | SHOWN? 230-2 |
| | |
| | 8)NOTE: PLEASE CLARIFY "DOOR" SHOWN IN- |
| | -FRONT OF STAIRS? |
| | |
| | 9)NOTE: PLEASE NOTE LOAD CALCULATIONS |
| | SHOW UNITS 1,2,4,5 AND THEN UNITS 4&6, |
| | PLEASE CLARIFY 2-#4 UNITS? IS THE UPPER |
| | #4 SUPPOSE TO BE #3 |
| | |
| | 10)NOTE: PLEASE ELECTRICAL PLANS DUE TO |
| | NOTES ON SIDE OF PLANS. |
| | |
| | |
| | PLEASE MAKE THE ABOVE CORRECTIONS, AND |
| | SUBMIT FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |