| Plan Review Notes For Permit 02010567 |
| Permit Number |
02010567 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-22 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) ROUTE PLANS TO PALM BEACH COUNTY | | | HEALTH UNIT DIVISION OF ENVIRONMENTAL | | | HEALTH 901 EVERNIA STREET, WPB FL 33401 | | | PHONE # (561) 355-3018. PLEASE ROUTE BE- | | | FORE PLAN REVIEW. | | | 2) EXISTING FLOOR PLAN REQUIRED FOR DEMO | | | 3) SHT A1. TURNING RADIUS TO BE SHOWN IN | | | REST ROOM NOT IN STALL. (SEE FIG. 30(E)) | | | PLEASE SHOW DETAIL ON PLANS. | | | 4) SHT P-1 OF 2, INDIRECT WASTE TO BE | | | DRAINED TO FLOOR SINK NOT FLOOR DRAIN. | | | SPC SEC 804.1 & 804.5 | | | 5) SHT P-2 0F 2 NOTES #'S 6 & 7 AIR | | | CHAMBERS ARE TEMPORY FIX AND SHALL HAVE | | | ACESS AND BE RECHARGEABLE PER SPC SEC | | | 607.8.3. WATER HAMMER ARRESTORS ARE RE- | | | COMMENDED. | | | 6) SHT P-2 OF 2 WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT AT TOP OF DROP AS | | | SHOWN. (SEE ATTACHED SHEET) LOCATE ARRES | | | TORS PER MANUFACTURES INSTALLATION INST- | | | RUCTIONS AND PDI-WH 201. | | | 7) SHT P-2 OF 2, WATER HEATER LOCATION | | | REQUIRES A PERMINATE SHIPS LADDER AND A | | | SERVICE PLATFORM, MIMIMUM OF 30"X30" AT | | | SERVICE SIDE OF WATER HEATER. SHOW DE- | | | TAILS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|