Plan Review Notes
Plan Review Notes For Permit 02010567
Permit Number 02010567
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-22 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) ROUTE PLANS TO PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH 901 EVERNIA STREET, WPB FL 33401
 PHONE # (561) 355-3018. PLEASE ROUTE BE-
 FORE PLAN REVIEW.
 2) EXISTING FLOOR PLAN REQUIRED FOR DEMO
 3) SHT A1. TURNING RADIUS TO BE SHOWN IN
 REST ROOM NOT IN STALL. (SEE FIG. 30(E))
 PLEASE SHOW DETAIL ON PLANS.
 4) SHT P-1 OF 2, INDIRECT WASTE TO BE
 DRAINED TO FLOOR SINK NOT FLOOR DRAIN.
 SPC SEC 804.1 & 804.5
 5) SHT P-2 0F 2 NOTES #'S 6 & 7 AIR
 CHAMBERS ARE TEMPORY FIX AND SHALL HAVE
 ACESS AND BE RECHARGEABLE PER SPC SEC
 607.8.3. WATER HAMMER ARRESTORS ARE RE-
 COMMENDED.
 6) SHT P-2 OF 2 WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT AT TOP OF DROP AS
 SHOWN. (SEE ATTACHED SHEET) LOCATE ARRES
 TORS PER MANUFACTURES INSTALLATION INST-
 RUCTIONS AND PDI-WH 201.
 7) SHT P-2 OF 2, WATER HEATER LOCATION
 REQUIRES A PERMINATE SHIPS LADDER AND A
 SERVICE PLATFORM, MIMIMUM OF 30"X30" AT
 SERVICE SIDE OF WATER HEATER. SHOW DE-
 TAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377