| Plan Review Notes For Permit 02010567 |
| Permit Number |
02010567 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-18 00:00:00 | ****************UNSAT!****************** | | | 1) PLEASE PROVIDE DEMOLITION PLANS | | | INDICATING REUSE OR TERMINATION OF | | | EXISTING WIRING. | | | 2) ONLY PAGE "EI OF 2" WAS SUBMITTED FOR | | | REVIEW ? | | | 3) PROVIDE LOAD CALCULATIONS FOR | | | EXISTING PANELS. | | | 4) PROVIDE LOAD CALCULATIONS FOR | | | ADDITION LOADS ON EXISTING PANELS. | | | 5) PROVIDE PLANS FOR ROOF TOP ACCU'S & | | | LOCATION OF REQUIRED GFI'S AS PER | | | 210-63NEC AND 309.2 SBCCI MECHANICAL | | | CODE. | | | 6) PROVIDE TITLE BLOCK ON PANEL | | | SCHEDULES PER 61G1-16.004. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT.8392 |
|