Plan Review Notes
Plan Review Notes For Permit 02010567
Permit Number 02010567
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC 1007.3.1STAIR TREADS AND RISERS
 SHALL BE SO PROPORTIONED THAT THE SUM OF
 TWO RISERS (2R) AND A TREAD (T),
 EXCLUSIVE OF NOSING PROJECTION, IS NOT
 LESS THAN 24" NOR MORE THAN 25".
 TYPICAL STEP DETAIL 5/A-2 SHOWS A 6"
 TYPICAL RISER HEIGHT.MULTIPLES OF 6"
 DO NOT CORRELATE TO THE REQUIRED DECK OR
 PRIVATE AREA HEIGHTS OF 14" AND 28" AFF
 RESPECTIVELY.AMEND THE TREAD/RISER
 RELATIONSHIP.NOTE THAT INCREASING THE
 RISER TO 7" WITH THE PROPOSED 13" TREAD
 WILL NOT COMPLY WITH THE REQUIREMENT FOR
 24"<=2R+T<=25".
  
 3) FL ACC CODE 4.32.3DETAIL 5/A-3,
 H.C. BAR STATION.THE WALL FIXTURE FOR
 THE BAR SUPPORT BRACKET, SHOWN ON THE
 CROSS-SECTION, SHALL NOT PROTRUDE INTO
 THE REQUIRED 27" HIGH BY 19" DEEP KNEE
 CLEARANCE SPACE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499