Plan Review Notes
Plan Review Notes For Permit 02010564
Permit Number 02010564
Review Stop E
Sequence Number 2
Notes
Date Text
2002-03-28 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT SHEET E-1
 HAS BEEN REVISED AND IS NOW SHOWING
 75 KVA TRANSFORMER "ABOVE"?? PLEASE
 CLARIFY IF ABOVE, IS ABOVE CEILING OR
 MOUNTED ON WALL ABOVE EQUIPMENT??
 450-13B.
  
 2)NOTE: PLEASE NOTE THAT METER LOCATION
 IS NOTED IN RESPONSE LETTER AS LOCATION
 CHANGED PER FIRST SET OF REVIEW NOTES
 AND STILL SEEMS MENTIONS BEING ABOVE?
 PLEASE NOTE THAT PER FPL REQ`MENTS AND
 STANDARDS, ELEC METER ARE NOT TO BE
 PLACED ABOVE CEILINGS OR ABOVE 6'5".
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372