| Plan Review Notes For Permit 02010564 |
| Permit Number |
02010564 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-28 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT SHEET E-1 | | | HAS BEEN REVISED AND IS NOW SHOWING | | | 75 KVA TRANSFORMER "ABOVE"?? PLEASE | | | CLARIFY IF ABOVE, IS ABOVE CEILING OR | | | MOUNTED ON WALL ABOVE EQUIPMENT?? | | | 450-13B. | | | | | | 2)NOTE: PLEASE NOTE THAT METER LOCATION | | | IS NOTED IN RESPONSE LETTER AS LOCATION | | | CHANGED PER FIRST SET OF REVIEW NOTES | | | AND STILL SEEMS MENTIONS BEING ABOVE? | | | PLEASE NOTE THAT PER FPL REQ`MENTS AND | | | STANDARDS, ELEC METER ARE NOT TO BE | | | PLACED ABOVE CEILINGS OR ABOVE 6'5". | | | PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|