Plan Review Notes
Plan Review Notes For Permit 02010564
Permit Number 02010564
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-31 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-1 SPC TABLE 407 REQUIRES TWO
 WATER CLOSETS AND TWO LAVS FOR WOMENS
 RESTROOM. 1 EA PROVIDED.
  
 2) SHT A-2 WATER FOUNTAIN DETAIL. PER
 FACBC SEC 4.1.3(10) PROVISIONS SHALL BE
 PROVIDED FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING. EITHER A HI/LOW DF
 OR PROVIDE CUP DISPENSER. SHOW DETAILS.
  
 3) SHT P-1 DOMESTIC WATER ISOMETRIC DIA.
 WATER HAMMER ARRESTORS TO BE LOCATED PER
 MANUFACTURE INSTALLATION INSTRUCTIONS &
 PDI-WH 201, IN AN "EFFECTIVE RANGE"
 CLOSE TO FIXTURE NOT ON TOP OF DROP AS
 SHOWN.
  
 4) SHT A-1 LOUNGE SINK. PLEASE PROVIDE
 DETAILS TO SHOW COMPLIANCE WITH FACBC
 SEC 4.24.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377