| Plan Review Notes For Permit 02010564 |
| Permit Number |
02010564 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-15 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW LOCATION OF TRANSFOR | | | MER. | | | | | | 2)NOTE: PLEASE SEE E-1, PLEASE CLARIFY | | | METER AND DISCONNECT AAS BEING "ABOVE" | | | CEILING??? | | | PLEASE NOTE ACCESSILE SERVICE EQUIPMENT? | | | | | | 3)NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN, PLEASE | | | NOTE THAT ALLCONTINUOUS LOADS ARE TO | | | SHOWN AT 125% 230-42 215-2. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|