Plan Review Notes
Plan Review Notes For Permit 02010564
Permit Number 02010564
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-15 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW LOCATION OF TRANSFOR
 MER.
  
 2)NOTE: PLEASE SEE E-1, PLEASE CLARIFY
 METER AND DISCONNECT AAS BEING "ABOVE"
 CEILING???
 PLEASE NOTE ACCESSILE SERVICE EQUIPMENT?
  
 3)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN, PLEASE
 NOTE THAT ALLCONTINUOUS LOADS ARE TO
 SHOWN AT 125% 230-42 215-2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372